Boiler
  Horizontal Fire Tube Boiler
  Vertical Steam Boiler
  Water Tube Boiler Type "D"
  Coal Fired Tube Builer
Industial Washer - Tumble Dryer - Hydro Extractor
Kiln Timber
Autoclave
Other Devices
Burner - Motor - Valve
   
Coal Fired Water Tube Boiler
 
 
  High efficiency
 High tech Design
 An environment - friendly product

1. Concrete plinth 13. Air vent
2. Water drum 14. Standby steam outlet
3. Header 15. Water level limiter
4. Pressure relay 16. Standby steam outlet
5. Pressure gauge 17. Safety valve
6. Steam piping into pressure gauge 18. Steam piping into pressure gauge
7. Level gauge 19. Main steam valve
8. Feed water piping 20 Standby steam outlet
9. Feed water pump 21. Steam drum
10. Cinder output door 22. Platform
11. Coal input door 23. Ladder
12. Blowdown valve 24. Flue exhaust
  SPECIFICATIONS
MODEL NO.

CB
100

CB
200
CB
500
CB
750
CB
1000
CB
1500
CB
2000
CB
2500
CB
3000
CB
4000
CB
5000
CB
6000
Capacity (KW)
60
120
300
500
600
1000
1300
1600
2000
2700
3300
4000
Evaporation (kg/h) at 100oC
100
200
500
750
1000
1500
2000
2500
3000
4000
5000
6000
Consumtion of coal (kg/h)
15
30
70
105
180
210
280
350
420
560
700
840
Heating surface (m2)
5.2
10.5
21.4
32
41.2
62.5
81.6
103.8
125.9
163.1
205.2
252
Overall hight (mm) A
1980
2510
3150
3260
3450
3680
3850
3920
4150
4150
4150
4150
Overall width (mm) B
920
1000
1200
1350
1500
1600
1800
1950
2200
2600
2850
3000
Overall length (mm) C
1500
1950
2400
2500
2750
2850
3000
3200
3400
3550
3820
4200
Main steam outlet
34
42
49
60
60
76
76
90
90
114
140
168
Feed water inlet
21
27
27
34
34
42
42
42
42
49
49
49
Safety valve
27
34
34
34
42
42
49
49
49
60
60
76
Blowdown valve
27
27
34
34
42
42
42
49
49
49
49
49
Chimney Diameter
150
200
265
268
320
340
360
400
420
480
550
630
 
 
  Office:
117A Binh Thoi, Ward.11, Dist. 11, HCMC
Tel: (84-8) - 962.9830 - 752.3634
Website: www.hongnhutco.com
Workshop:
150C Ho Hoc Lam, An Lac Ward., Binh Tan Dist., HCMC
Tel: (84-8)-875.9133 Fax: (84-8)-750.9836
Email: hongnhutcoltd@hcm.vnn.vn